Back to the backflow review queue

Backflow assembly test: 7268 Laurel Trl

Approved

Filed Jun 6, 2024 by Emerson Calloway, Ridge Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jun 6, 2024
Assembly type
DC
Serial number
W538133
Size
3/4
Test gauge serial
G-7271
Gauge calibration date
Nov 9, 2023
Check valve 1
0.2 psid
Check valve 1 closed tight
No
Check valve 2
3.8 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Emerson Calloway, current on the service date
  • All required fields present
  • Address matches parcel 055-17-01232
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

7268 Laurel Trl
Owner: Cameron Hollins
Parcel 055-17-01232