Back to the backflow review queue

Backflow assembly test: Two Rivers Brewing Co

Approved

Filed Sep 15, 2025 by Hayden Fairley, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
Sep 15, 2025
Assembly type
RP
Serial number
Z793420
Size
1
Test gauge serial
G-9841
Gauge calibration date
Dec 23, 2024
Check valve 1
3.7 psid
Check valve 1 closed tight
Yes
Check valve 2
2.3 psid
Relief valve opened at
3.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Hayden Fairley, current on the service date
  • All required fields present
  • Address matches parcel 055-62-01347
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

7287 Mill Creek Ln
Owner: Brandt Holdings LLC
Parcel 055-62-01347