Backflow assembly test: 3955 Meadow Lark Rd
ApprovedFiled Feb 14, 2025 by Parker Brandt, Heritage Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Feb 14, 2025
- Assembly type
- RP
- Serial number
- Z628027
- Size
- 3/4
- Test gauge serial
- G-1833
- Gauge calibration date
- Oct 17, 2023
- Check valve 1
- 0.4 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 2.4 psid
- Relief valve opened at
- 2.4 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Brandt, current on the service date
- All required fields present
- Address matches parcel 055-80-01281
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.