Backflow assembly test: Station Self Storage
ApprovedFiled Mar 18, 2026 by Emerson Calloway, Ridge Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Mar 18, 2026
- Assembly type
- RP
- Serial number
- K651457
- Size
- 1 1/2
- Test gauge serial
- G-9664
- Gauge calibration date
- Jul 4, 2025
- Check valve 1
- 7.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.6 psid
- Relief valve opened at
- 2.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Emerson Calloway, current on the service date
- All required fields present
- Address matches parcel 055-20-01350
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
2068 Stone Gate Ln
Owner: Stroud Holdings LLC
Parcel 055-20-01350