Back to the backflow review queue
Backflow assembly test: Crossroads Market
ApprovedFiled Sep 27, 2025 by Riley Calloway, Northstar Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Sep 27, 2025
- Assembly type
- RP
- Serial number
- Z219039
- Size
- 1 1/2
- Test gauge serial
- G-9843
- Gauge calibration date
- Mar 4, 2025
- Check valve 1
- 6.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.8 psid
- Relief valve opened at
- 2.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Riley Calloway, current on the service date
- All required fields present
- Address matches parcel 059-85-01344
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
2600 Orchard Rd
Owner: Marsh Holdings LLC
Parcel 059-85-01344