Backflow assembly test: Riverside Brewing Co
ApprovedFiled Dec 16, 2023 by Avery Ramirez, Patriot Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Dec 16, 2023
- Assembly type
- RP
- Serial number
- B520112
- Size
- 4
- Test gauge serial
- G-9354
- Gauge calibration date
- Mar 20, 2023
- Check valve 1
- 5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.5 psid
- Relief valve opened at
- 3.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Avery Ramirez, current on the service date
- All required fields present
- Address matches parcel 059-23-01031
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.