Back to the backflow review queue

Backflow assembly test: Main Street Self Storage

Approved

Filed Jan 5, 2026 by Logan Stroud, Ridge Backflow Testing. Filed from a phone.

Report

Date of service
Jan 5, 2026
Assembly type
DC
Serial number
W933783
Size
2
Test gauge serial
G-2438
Gauge calibration date
May 30, 2025
Check valve 1
6.8 psid
Check valve 1 closed tight
Yes
Check valve 2
1.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Logan Stroud, current on the service date
  • All required fields present
  • Address matches parcel 059-79-01130
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

4185 Mill Creek Way
Owner: Fairley Holdings LLC
Parcel 059-79-01130