Back to the backflow review queue

Backflow assembly test: Golden Elementary School

Filed Nov 26, 2026 by Riley Calloway, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
Nov 26, 2026
Assembly type
RP
Serial number
W221839
Size
1 1/2
Test gauge serial
G-7136
Gauge calibration date
Oct 3, 2026
Check valve 1
7.3 psid
Check valve 1 closed tight
Yes
Check valve 2
1.3 psid
Relief valve opened at
4.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Riley Calloway, current on the service date
  • All required fields present
  • Address matches parcel 059-68-01314
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Property

261 Turkey Hill Ln
Owner: Brandt Holdings LLC
Parcel 059-68-01314