Backflow assembly test: 6887 Spring Branch Rd
ApprovedFiled May 6, 2026 by Riley Calloway, Northstar Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- May 6, 2026
- Assembly type
- RP
- Serial number
- K409889
- Size
- 3/4
- Test gauge serial
- G-2682
- Gauge calibration date
- Sep 25, 2025
- Check valve 1
- 0.4 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 1.1 psid
- Relief valve opened at
- 3.2 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Riley Calloway, current on the service date
- All required fields present
- Address matches parcel 059-75-01151
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
6887 Spring Branch Rd
Owner: Logan Okafor
Parcel 059-75-01151