Back to the backflow review queue

Backflow assembly test: 3193 Old Church Rd

Approved

Filed Sep 20, 2025 by Riley Calloway, Northstar Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Sep 20, 2025
Assembly type
RP
Serial number
K364413
Size
3/4
Test gauge serial
G-7275
Gauge calibration date
Mar 10, 2025
Check valve 1
8.4 psid
Check valve 1 closed tight
Yes
Check valve 2
3.5 psid
Relief valve opened at
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Riley Calloway, current on the service date
  • All required fields present
  • Address matches parcel 059-49-01109
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

3193 Old Church Rd
Owner: Alex Okafor
Parcel 059-49-01109