Back to the backflow review queue

Backflow assembly test: Main Street Self Storage

Filed Nov 22, 2026 by Logan Stroud, Ridge Backflow Testing. Filed from a phone.

Report

Date of service
Nov 22, 2026
Assembly type
DC
Serial number
A778655
Size
1
Test gauge serial
G-4196
Gauge calibration date
Apr 26, 2026
Check valve 1
5.3 psid
Check valve 1 closed tight
Yes
Check valve 2
1.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Logan Stroud, current on the service date
  • All required fields present
  • Address matches parcel 059-42-01164
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Property

9838 Hickory Rd
Owner: Calloway Holdings LLC
Parcel 059-42-01164