Backflow assembly test: 8607 Hickory Way

Approved

Filed Jul 12, 2024 by Logan Stroud, Ridge Backflow Testing. Filed from a phone.

Report

Date of service
Jul 12, 2024
Assembly type
RP
Serial number
Z102910
Size
1
Test gauge serial
G-7996
Gauge calibration date
Mar 14, 2024
Check valve 1
5.3 psid
Check valve 1 closed tight
Yes
Check valve 2
3.5 psid
Relief valve opened at
3.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Logan Stroud, current on the service date
  • All required fields present
  • Address matches parcel 059-62-01110
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

8607 Hickory Way
Owner: Emerson Nguyen
Parcel 059-62-01110