Back to the backflow review queue

Backflow assembly test: Riverside Apartments

Approved

Filed Jun 13, 2025 by Riley Calloway, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jun 13, 2025
Assembly type
RP
Serial number
Z420783
Size
1 1/2
Test gauge serial
G-8694
Gauge calibration date
Dec 2, 2024
Check valve 1
7.2 psid
Check valve 1 closed tight
Yes
Check valve 2
3.2 psid
Relief valve opened at
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Riley Calloway, current on the service date
  • All required fields present
  • Address matches parcel 059-20-01153
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

4407 Stone Gate Dr
Owner: Ramirez Holdings LLC
Parcel 059-20-01153