Back to the backflow review queue
Backflow assembly test: 3101 Meadow Lark Way
ApprovedFiled Mar 11, 2025 by Riley Calloway, Northstar Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Mar 11, 2025
- Assembly type
- RP
- Serial number
- A516884
- Size
- 3/4
- Test gauge serial
- G-7662
- Gauge calibration date
- Sep 19, 2024
- Check valve 1
- 4.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.3 psid
- Relief valve opened at
- 3.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Riley Calloway, current on the service date
- All required fields present
- Address matches parcel 059-68-01249
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
3101 Meadow Lark Way
Owner: Taylor Stroud
Parcel 059-68-01249