Back to the backflow review queue

Backflow assembly test: 3734 Ridgeview Dr

Approved

Filed Apr 13, 2025 by Avery Ramirez, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
Apr 13, 2025
Assembly type
DC
Serial number
Z139465
Size
3/4
Test gauge serial
G-2072
Gauge calibration date
Sep 14, 2024
Check valve 1
5.8 psid
Check valve 1 closed tight
Yes
Check valve 2
1 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Ramirez, current on the service date
  • All required fields present
  • Address matches parcel 059-21-01248
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.