Back to the backflow review queue
Backflow assembly test: 4474 Ridgeview Rd
ApprovedFiled Jul 2, 2026 by Riley Calloway, Northstar Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Jul 2, 2026
- Assembly type
- RP
- Serial number
- K415785
- Size
- 1
- Test gauge serial
- G-4230
- Gauge calibration date
- Dec 20, 2025
- Check valve 1
- 6.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.6 psid
- Relief valve opened at
- 4.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Riley Calloway, current on the service date
- All required fields present
- Address matches parcel 059-12-01111
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
4474 Ridgeview Rd
Owner: Logan Harlow
Parcel 059-12-01111