Backflow assembly test: 4883 Laurel Rd

Approved

Filed Oct 13, 2024 by Casey Pruitt, Clearwater Plumbing & Backflow. Filed from a phone.

Report

Date of service
Oct 13, 2024
Assembly type
RP
Serial number
W325606
Size
1
Test gauge serial
G-8496
Gauge calibration date
Jul 3, 2024
Check valve 1
4.3 psid
Check valve 1 closed tight
Yes
Check valve 2
3.9 psid
Relief valve opened at
3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Casey Pruitt, current on the service date
  • All required fields present
  • Address matches parcel 061-85-01020
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

4883 Laurel Rd
Owner: Jamie Pruitt
Parcel 061-85-01020