Backflow assembly test: 187 Meadow Lark Trl

Approved

Filed Feb 17, 2026 by Taylor Ashby, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Feb 17, 2026
Assembly type
RP
Serial number
B202135
Size
3/4
Test gauge serial
G-2174
Gauge calibration date
Dec 14, 2024
Check valve 1
0.7 psid
Check valve 1 closed tight
No
Check valve 2
1.1 psid
Relief valve opened at
2.9 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Taylor Ashby, current on the service date
  • All required fields present
  • Address matches parcel 061-69-01236
  • Test gauge calibration is more than a year old.
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

187 Meadow Lark Trl
Owner: Taylor Ramirez
Parcel 061-69-01236