Back to the backflow review queue

Backflow assembly test: Maple Leaf Grill

Approved

Filed Apr 13, 2023 by Avery Calloway, Clearwater Plumbing & Backflow. Filed from a phone.

Report

Date of service
Apr 13, 2023
Assembly type
RP
Serial number
A324930
Size
1 1/2
Test gauge serial
G-8553
Gauge calibration date
Dec 12, 2022
Check valve 1
8.2 psid
Check valve 1 closed tight
Yes
Check valve 2
3.8 psid
Relief valve opened at
3.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Calloway, current on the service date
  • All required fields present
  • Address matches parcel 061-39-01051
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

1505 Pine Knoll Dr
Owner: Danner Holdings LLC
Parcel 061-39-01051