Back to the backflow review queue
Backflow assembly test: Hilltop Pizza
ApprovedFiled Apr 14, 2026 by Taylor Ashby, Valley Backflow Testing. Filed from a phone.
Report
- Date of service
- Apr 14, 2026
- Assembly type
- RP
- Serial number
- K553336
- Size
- 1
- Test gauge serial
- G-5173
- Gauge calibration date
- Mar 9, 2026
- Check valve 1
- 6.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.2 psid
- Relief valve opened at
- 2.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Taylor Ashby, current on the service date
- All required fields present
- Address matches parcel 061-60-01213
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
4655 Pine Knoll Way
Owner: Okafor Holdings LLC
Parcel 061-60-01213