Backflow assembly test: Blue Heron Taqueria

Approved

Filed Oct 18, 2025 by Taylor Ashby, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Oct 18, 2025
Assembly type
RP
Serial number
Z796636
Size
1 1/2
Test gauge serial
G-3321
Gauge calibration date
Jul 23, 2025
Check valve 1
7.5 psid
Check valve 1 closed tight
Yes
Check valve 2
1.2 psid
Relief valve opened at
3.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Taylor Ashby, current on the service date
  • All required fields present
  • Address matches parcel 061-44-01319
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

2143 Old Church Ln
Owner: Marsh Holdings LLC
Parcel 061-44-01319