Back to the backflow review queue

Backflow assembly test: 7908 Pine Knoll Ln

Approved

Filed Dec 30, 2025 by Alex Benton, Clearwater Plumbing & Backflow. Filed from a phone.

Report

Date of service
Dec 30, 2025
Assembly type
DC
Serial number
Z111387
Size
1
Test gauge serial
G-2269
Gauge calibration date
Sep 10, 2025
Check valve 1
5.3 psid
Check valve 1 closed tight
Yes
Check valve 2
1.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Alex Benton, current on the service date
  • All required fields present
  • Address matches parcel 061-13-01240
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

7908 Pine Knoll Ln
Owner: Blake Whitcomb
Parcel 061-13-01240