Backflow assembly test: 8699 Laurel Trl
ApprovedFiled Jun 28, 2024 by Alex Benton, Clearwater Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Jun 28, 2024
- Assembly type
- RP
- Serial number
- B275804
- Size
- 3/4
- Test gauge serial
- G-3054
- Gauge calibration date
- Sep 29, 2023
- Check valve 1
- 5.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.1 psid
- Relief valve opened at
- 3.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Alex Benton, current on the service date
- All required fields present
- Address matches parcel 061-75-01071
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.