Back to the backflow review queue

Backflow assembly test: Maple Leaf Pizza

Approved

Filed Jan 4, 2024 by Alex Benton, Clearwater Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jan 4, 2024
Assembly type
DC
Serial number
A202632
Size
4
Test gauge serial
G-2038
Gauge calibration date
Sep 17, 2022
Check valve 1
5.4 psid
Check valve 1 closed tight
Yes
Check valve 2
1.8 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Alex Benton, current on the service date
  • All required fields present
  • Address matches parcel 061-11-01185
  • Test gauge calibration is more than a year old.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.