Backflow assembly test: 224 Sycamore Trl
ApprovedFiled Jan 29, 2024 by Avery Calloway, Clearwater Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Jan 29, 2024
- Assembly type
- RP
- Serial number
- W224169
- Size
- 1
- Test gauge serial
- G-4629
- Gauge calibration date
- Nov 7, 2023
- Check valve 1
- 6.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.9 psid
- Relief valve opened at
- 1.4 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Avery Calloway, current on the service date
- All required fields present
- Address matches parcel 061-40-01108
- RP relief valve must open at 2.0 psid or more.
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.