Backflow assembly test: 224 Sycamore Trl

Approved

Filed Jan 29, 2024 by Avery Calloway, Clearwater Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jan 29, 2024
Assembly type
RP
Serial number
W224169
Size
1
Test gauge serial
G-4629
Gauge calibration date
Nov 7, 2023
Check valve 1
6.3 psid
Check valve 1 closed tight
Yes
Check valve 2
1.9 psid
Relief valve opened at
1.4 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Calloway, current on the service date
  • All required fields present
  • Address matches parcel 061-40-01108
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

224 Sycamore Trl
Owner: Sam Danner
Parcel 061-40-01108