Back to the backflow review queue
Backflow assembly test: 224 Sycamore Trl
ApprovedFiled Feb 28, 2025 by Taylor Ashby, Valley Backflow Testing. Filed from a phone.
Report
- Date of service
- Feb 28, 2025
- Assembly type
- RP
- Serial number
- W224169
- Size
- 1
- Test gauge serial
- G-9399
- Gauge calibration date
- Nov 10, 2024
- Check valve 1
- 7.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.7 psid
- Relief valve opened at
- 2.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Taylor Ashby, current on the service date
- All required fields present
- Address matches parcel 061-40-01108
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
224 Sycamore Trl
Owner: Sam Danner
Parcel 061-40-01108