Back to the backflow review queue

Backflow assembly test: 9320 Turkey Hill Ln

Approved

Filed Jan 22, 2024 by Jamie Kessler, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Jan 22, 2024
Assembly type
RP
Serial number
Z242805
Size
1
Test gauge serial
G-6688
Gauge calibration date
Dec 22, 2023
Check valve 1
6.8 psid
Check valve 1 closed tight
Yes
Check valve 2
1.4 psid
Relief valve opened at
3.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jamie Kessler, current on the service date
  • All required fields present
  • Address matches parcel 061-46-01308
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

9320 Turkey Hill Ln
Owner: Alex Hollins
Parcel 061-46-01308