Back to the backflow review queue
Backflow assembly test: 4920 Laurel Trl
ApprovedFiled Feb 13, 2026 by Casey Pruitt, Clearwater Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Feb 13, 2026
- Assembly type
- PVB
- Serial number
- B700237
- Size
- 3/4
- Test gauge serial
- G-9276
- Gauge calibration date
- Aug 8, 2025
- Check valve 1
- 5.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Casey Pruitt, current on the service date
- All required fields present
- Address matches parcel 061-30-01042
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
4920 Laurel Trl
Owner: Logan Pruitt
Parcel 061-30-01042