Backflow assembly test: 3093 Laurel Dr

Approved

Filed Sep 21, 2026 by Blake Harlow, Evergreen Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Sep 21, 2026
Assembly type
RP
Serial number
B539344
Size
3/4
Test gauge serial
G-7351
Gauge calibration date
Dec 2, 2025
Check valve 1
5.7 psid
Check valve 1 closed tight
Yes
Check valve 2
3.7 psid
Relief valve opened at
3.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Blake Harlow, current on the service date
  • All required fields present
  • Address matches parcel 065-39-01317
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.