Backflow assembly test: 6197 Laurel Ct

Approved

Filed Dec 15, 2023 by Reese Lindqvist, Valley Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Dec 15, 2023
Assembly type
DC
Serial number
B576824
Size
3/4
Test gauge serial
G-5034
Gauge calibration date
Apr 28, 2023
Check valve 1
3.5 psid
Check valve 1 closed tight
Yes
Check valve 2
2.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Lindqvist, current on the service date
  • All required fields present
  • Address matches parcel 065-34-01180
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

6197 Laurel Ct
Owner: Quinn Nguyen
Parcel 065-34-01180