Backflow assembly test: 6197 Laurel Ct
ApprovedFiled Dec 23, 2024 by Blake Brandt, Clearwater Backflow Testing. Filed from a phone.
Report
- Date of service
- Dec 23, 2024
- Assembly type
- DC
- Serial number
- B576824
- Size
- 3/4
- Test gauge serial
- G-1187
- Gauge calibration date
- Sep 19, 2024
- Check valve 1
- 5.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Blake Brandt, current on the service date
- All required fields present
- Address matches parcel 065-34-01180
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
6197 Laurel Ct
Owner: Quinn Nguyen
Parcel 065-34-01180