Backflow assembly test: 820 Quarry Trl

Approved

Filed Aug 9, 2026 by Alex Wexler, Clearwater Backflow Testing. Filed from a phone.

Report

Date of service
Aug 9, 2026
Assembly type
RP
Serial number
A495318
Size
3/4
Test gauge serial
G-5145
Gauge calibration date
Apr 30, 2026
Check valve 1
3.6 psid
Check valve 1 closed tight
Yes
Check valve 2
3.8 psid
Relief valve opened at
2.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Alex Wexler, current on the service date
  • All required fields present
  • Address matches parcel 065-75-01249
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.