Back to the backflow review queue

Backflow assembly test: 466 Pine Knoll Way

Approved

Filed Feb 20, 2026 by Blake Harlow, Evergreen Plumbing & Backflow. Filed from a phone.

Report

Date of service
Feb 20, 2026
Assembly type
RP
Serial number
Z388088
Size
3/4
Test gauge serial
G-9994
Gauge calibration date
Apr 30, 2025
Check valve 1
7.1 psid
Check valve 1 closed tight
Yes
Check valve 2
1.1 psid
Relief valve opened at
3.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Blake Harlow, current on the service date
  • All required fields present
  • Address matches parcel 065-33-01308
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

466 Pine Knoll Way
Owner: Hayden Whitcomb
Parcel 065-33-01308