Backflow assembly test: 7313 Fox Run Dr
ApprovedFiled Aug 20, 2026 by Reese Lindqvist, Valley Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Aug 20, 2026
- Assembly type
- RP
- Serial number
- A167394
- Size
- 3/4
- Test gauge serial
- G-1984
- Gauge calibration date
- Jul 9, 2025
- Check valve 1
- 7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.6 psid
- Relief valve opened at
- 1.6 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Reese Lindqvist, current on the service date
- All required fields present
- Address matches parcel 065-48-01266
- RP relief valve must open at 2.0 psid or more.
- Test gauge calibration is more than a year old.
- Result: passing. Next due date resets when approved.