Backflow assembly test: 8942 Pine Knoll Trl

Approved

Filed May 10, 2024 by Alex Wexler, Clearwater Backflow Testing. Filed from a phone.

Report

Date of service
May 10, 2024
Assembly type
RP
Serial number
A858691
Size
1
Test gauge serial
G-1804
Gauge calibration date
Jan 1, 2024
Check valve 1
8.5 psid
Check valve 1 closed tight
Yes
Check valve 2
1.8 psid
Relief valve opened at
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Alex Wexler, current on the service date
  • All required fields present
  • Address matches parcel 065-51-01347
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.