Back to the backflow review queue

Backflow assembly test: 8942 Pine Knoll Trl

Approved

Filed Jun 3, 2025 by Blake Brandt, Clearwater Backflow Testing. Filed from a phone.

Report

Date of service
Jun 3, 2025
Assembly type
RP
Serial number
A858691
Size
1
Test gauge serial
G-2087
Gauge calibration date
Apr 16, 2024
Check valve 1
0 psid
Check valve 1 closed tight
No
Check valve 2
3.6 psid
Relief valve opened at
3.8 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Blake Brandt, current on the service date
  • All required fields present
  • Address matches parcel 065-51-01347
  • Test gauge calibration is more than a year old.
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

8942 Pine Knoll Trl
Owner: Hayden Danner
Parcel 065-51-01347