Back to the backflow review queue

Backflow assembly test: 4792 Hickory Ct

Approved

Filed Dec 31, 2023 by Alex Wexler, Clearwater Backflow Testing. Filed from a phone.

Report

Date of service
Dec 31, 2023
Assembly type
DC
Serial number
W150736
Size
1
Test gauge serial
G-7993
Gauge calibration date
Jun 17, 2023
Check valve 1
7.6 psid
Check valve 1 closed tight
Yes
Check valve 2
2.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Alex Wexler, current on the service date
  • All required fields present
  • Address matches parcel 065-97-01191
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

4792 Hickory Ct
Owner: Riley Danner
Parcel 065-97-01191