Backflow assembly test: Hilltop Diner

Approved

Filed Aug 16, 2026 by Morgan Wexler, Evergreen Plumbing & Backflow. Filed from a phone.

Report

Date of service
Aug 16, 2026
Assembly type
RP
Serial number
B843546
Size
2
Test gauge serial
G-4928
Gauge calibration date
Jan 27, 2026
Check valve 1
6.3 psid
Check valve 1 closed tight
Yes
Check valve 2
1.6 psid
Relief valve opened at
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Morgan Wexler, current on the service date
  • All required fields present
  • Address matches parcel 065-22-01294
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

2956 Orchard Rd
Owner: Pruitt Holdings LLC
Parcel 065-22-01294