Backflow assembly test: 9291 Orchard Rd

Approved

Filed Oct 4, 2026 by Alex Wexler, Clearwater Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Oct 4, 2026
Assembly type
PVB
Serial number
B174226
Size
1
Test gauge serial
G-9992
Gauge calibration date
Oct 4, 2025
Check valve 1
8.8 psid
Check valve 1 closed tight
Yes
Check valve 2
3.8 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Alex Wexler, current on the service date
  • All required fields present
  • Address matches parcel 065-47-01306
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

9291 Orchard Rd
Owner: Drew Lindqvist
Parcel 065-47-01306