Backflow assembly test: 8648 Meadow Lark Trl
ApprovedFiled Aug 16, 2025 by Reese Lindqvist, Valley Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Aug 16, 2025
- Assembly type
- PVB
- Serial number
- K111325
- Size
- 3/4
- Test gauge serial
- G-7981
- Gauge calibration date
- Feb 24, 2025
- Check valve 1
- 8.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Reese Lindqvist, current on the service date
- All required fields present
- Address matches parcel 065-62-01077
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
8648 Meadow Lark Trl
Owner: Morgan Okafor
Parcel 065-62-01077