Backflow assembly test: Hilltop Medical Offices

Approved

Filed May 26, 2025 by Parker Okafor, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
May 26, 2025
Assembly type
RP
Serial number
A794799
Size
1
Test gauge serial
G-8587
Gauge calibration date
Jan 24, 2025
Check valve 1
8.3 psid
Check valve 1 closed tight
Yes
Check valve 2
2.8 psid
Relief valve opened at
3.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Okafor, current on the service date
  • All required fields present
  • Address matches parcel 065-41-01355
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

2995 Ridgeview Trl
Owner: Calloway Holdings LLC
Parcel 065-41-01355