Backflow assembly test: Crossroads Bakery

Approved

Filed Apr 12, 2025 by Parker Okafor, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Apr 12, 2025
Assembly type
DC
Serial number
W939825
Size
1 1/2
Test gauge serial
G-3423
Gauge calibration date
Jan 21, 2025
Check valve 1
4.9 psid
Check valve 1 closed tight
Yes
Check valve 2
3.8 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Okafor, current on the service date
  • All required fields present
  • Address matches parcel 065-65-01207
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.