Back to the backflow review queue

Backflow assembly test: 2920 Turkey Hill Rd

Approved

Filed Mar 6, 2025 by Blake Harlow, Evergreen Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Mar 6, 2025
Assembly type
RP
Serial number
K143245
Size
1
Test gauge serial
G-9623
Gauge calibration date
Dec 3, 2024
Check valve 1
4.6 psid
Check valve 1 closed tight
Yes
Check valve 2
1.5 psid
Relief valve opened at
1.1 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Blake Harlow, current on the service date
  • All required fields present
  • Address matches parcel 065-58-01314
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

2920 Turkey Hill Rd
Owner: Taylor Nguyen
Parcel 065-58-01314