Backflow assembly test: 9597 Ridgeview Rd
ApprovedFiled Mar 5, 2026 by Parker Okafor, Valley Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Mar 5, 2026
- Assembly type
- RP
- Serial number
- Z772059
- Size
- 1
- Test gauge serial
- G-7752
- Gauge calibration date
- Sep 30, 2025
- Check valve 1
- 3.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.8 psid
- Relief valve opened at
- 3.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Okafor, current on the service date
- All required fields present
- Address matches parcel 065-37-01348
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
9597 Ridgeview Rd
Owner: Avery Ellery
Parcel 065-37-01348