Backflow assembly test: Maple Leaf Bakery

Approved

Filed Jun 18, 2026 by Quinn Wexler, Lakeside Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jun 18, 2026
Assembly type
RP
Serial number
A450558
Size
2
Test gauge serial
G-4985
Gauge calibration date
Dec 8, 2025
Check valve 1
7.6 psid
Check valve 1 closed tight
Yes
Check valve 2
2 psid
Relief valve opened at
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Quinn Wexler, current on the service date
  • All required fields present
  • Address matches parcel 067-74-01189
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.