Back to the backflow review queue

Backflow assembly test: Station Medical Offices

Approved

Filed Sep 30, 2025 by Quinn Wexler, Lakeside Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Sep 30, 2025
Assembly type
RP
Serial number
B376140
Size
1
Test gauge serial
G-6701
Gauge calibration date
Jan 25, 2025
Check valve 1
4.5 psid
Check valve 1 closed tight
Yes
Check valve 2
2.5 psid
Relief valve opened at
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Quinn Wexler, current on the service date
  • All required fields present
  • Address matches parcel 067-64-01147
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

1662 Spring Branch Trl
Owner: Benton Holdings LLC
Parcel 067-64-01147