Backflow assembly test: 2051 Fox Run Dr
ApprovedFiled Apr 21, 2025 by Avery Benton, Keystone Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Apr 21, 2025
- Assembly type
- RP
- Serial number
- W319767
- Size
- 3/4
- Test gauge serial
- G-1492
- Gauge calibration date
- May 6, 2024
- Check valve 1
- 7.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.7 psid
- Relief valve opened at
- 1.3 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Avery Benton, current on the service date
- All required fields present
- Address matches parcel 067-83-01299
- RP relief valve must open at 2.0 psid or more.
- Result: passing. Next due date resets when approved.