Backflow assembly test: 2051 Fox Run Dr

Approved

Filed May 14, 2026 by Reese Danner, Keystone Plumbing & Backflow. Filed from a phone.

Report

Date of service
May 14, 2026
Assembly type
RP
Serial number
W319767
Size
3/4
Test gauge serial
G-1791
Gauge calibration date
Feb 22, 2026
Check valve 1
8.8 psid
Check valve 1 closed tight
Yes
Check valve 2
2 psid
Relief valve opened at
3.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Danner, current on the service date
  • All required fields present
  • Address matches parcel 067-83-01299
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

2051 Fox Run Dr
Owner: Taylor Hollins
Parcel 067-83-01299