Back to the backflow review queue

Backflow assembly test: 6296 Orchard Ct

Approved

Filed Jun 26, 2023 by Quinn Wexler, Lakeside Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jun 26, 2023
Assembly type
RP
Serial number
A926653
Size
3/4
Test gauge serial
G-4928
Gauge calibration date
Apr 5, 2023
Check valve 1
4.6 psid
Check valve 1 closed tight
Yes
Check valve 2
2.7 psid
Relief valve opened at
1.2 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Quinn Wexler, current on the service date
  • All required fields present
  • Address matches parcel 067-14-01283
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

6296 Orchard Ct
Owner: Hayden Danner
Parcel 067-14-01283