Backflow assembly test: 6583 Sycamore Ct
ApprovedFiled Apr 5, 2026 by Quinn Wexler, Lakeside Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Apr 5, 2026
- Assembly type
- RP
- Serial number
- A549523
- Size
- 3/4
- Test gauge serial
- G-1961
- Gauge calibration date
- Jan 5, 2026
- Check valve 1
- 6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.8 psid
- Relief valve opened at
- 3.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Quinn Wexler, current on the service date
- All required fields present
- Address matches parcel 067-35-01297
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
6583 Sycamore Ct
Owner: Sam Kessler
Parcel 067-35-01297